Table of Contents Table of Contents
Previous Page  17 / 66 Next Page
Information
Show Menu
Previous Page 17 / 66 Next Page
Page Background www.siechem.com

16

Singlecore GI Wire Braided Anti-Rodent Solar DC Cables

Nominal

Insulation

Thickness

Max. DC Conductor

Resistance

at 20°C

Cable

Diameter

(Nom)

Cable Weight

(Nom)

Current Rating for

Two Loaded Cables

Touching on Surfaces

Cross

Section

Area

Part Number

Sq.mm

mm

mm

Kg/Km

Amps

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

*Note : Insulations colour (XX) - Please add two digits in the part number as per the colour code given hereunder replacing XX while ordering

Red - 01, Black - 04, White - 09

Sheath Colour (YY) please add two digits in the part number as per the colour code given hereunder replacing YY while ordering

Red - 01, Blue - 03, Black - 04, Brown - 08, Grey - 07, Black / Red - 39*

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

13.7

8.21

5.09

3.39

1.95

1.24

0.795

0.565

0.393

0.277

0.210

0.164

0.132

0.108

0.0817

9.5 ± 0.9

10.0 ± 1.0

11.0 ± 1.1

11.5 ± 1.2

12.5 ± 1.3

14.0 ± 1.4

15.5 ± 1.6

16.5 ± 1.7

18.5 ± 1.9

20.5 ± 2.1

22.0 ± 2.2

24.0 ± 2.4

26.0 ± 2.6

29.0 ± 2.9

31.5 ± 3.2

145

160

195

225

280

360

485

600

785

995

1240

1500

1830

2235

2770

24

33

44

57

79

107

142

176

221

278

333

390

453

515

620

Ω/km

B56713XXYY

B56716XXYY

B56719XXYY

B56723XXYY

B56727XXYY

B56728XXYY

B56730XXYY

B56732XXYY

B56734XXYY

B56737XXYY

B56738XXYY

B56741XXYY

B56742XXYY

B56744XXYY

B56746XXYY

Wires & Cables

Single Core Anti-Rodent GI Wire Braided Flexible Copper Conductor Electron Beam Irradiated Solar DC Cable

Generally as per EN 50618

Construction

Features

Conductor

Insulation

Inner Sheath

Outer Sheath

Braiding

:

:

:

:

:

Annealed Tinned Copper (APC Optional)

according to IEC 60228, Class 5 or as per

customer order

EBXL - XLPO 120ºC (UV Resistant)

EBXL - XLPO 120º C Highly Weather &

UV Resistant (Colour Black, Blue, Red, Brown,

Grey, Black with Red stripe)

EBXL - XLPO 120°C (Colour White, Red & Black)

Other colours as per customer order

Single Core

Siechem Solar Cable Range

Type of Solar cables

Siechem Single & Multicore Solar Cables meets specification

EN 50618

Siechem Single & Multicore Solar Cables meets specification

UL 4703

Siechem Single & Multicore Solar Cables to meet both

EN & UL specification

1.5 to

240sq.mm

or its equivalent size in AWG

:

Anti-Termite and Anti-Rodent Properties

Resistance against UV, Water, Ozone, Fluids, Oil, Salt &

General Weathering.

Electron Beam Cross Linked

Halogen Free, Flame Retardant, Low Smoke Emission

Fire retardant to meet IEC 607541-1/EN 50268-2

RoHS compliant as per EU norms

Max.Temp. at Conductor

Test Voltage

Voltage Resistance Test

Rated Voltage

Short Circuit Temp

: 6500V AC for 5 minutes

:

:

+280°C

:

EN 50395

120°C (20,000h)

:

Nominal

Inner Sheath

Thickness

Braiding

Wire Dia

(Nom)

Nominal

Outer Sheath

Thickness

0.8

0.8

0.8

0.8

0.8

0.9

1.0

1.1

1.2

1.2

1.3

1.3

1.4

1.6

1.7

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

1.4

1.4

1.4

1.4

1.4

1.4

1.5

1.5

1.6

1.6

1.6

1.7

1.8

1.8

1.8

mm

mm

mm

1.0/1.0kV AC,1.5kV DC

SiechemEBXLXLPO120°C GIWireBraidedCopperENSpecificationSolarCable

GI Wire

Catalogue

No

B567

TUV

AS

9100

ISO

45001

ISO

9001

ISO

14001