Rated Voltage : 1/1 kV AC (1.5/1.5 kV DC Nom)
ü
Max. Permitted Operating Voltage : 1.8kV DC
ü
Temperature Range : -40 ºC to +120 ºC
ü
Current Carrying Capacity :
(i) In Ground at 30ºC : 47 A
(ii) In Duct at 30ºC : 41A
(iii) In air at 60ºC : 44A
(iv) Two cables adjacent on surface : 44A
ü
Short Circuit Capacity for 1 sec : 0.552 kA
ü
Current Carrying Capacity :
(i) Max. Conductor temperature at rated current : 90ºC
(ii) Ambient Air Temperature : 45ºC
(iii) Ambient Soil temperature : 30ºC
(iv) Over load capacity : 130ºC
ü
Max. Continuous working temp : 120º C
ü
Max. Conductor temperature at rated current : 90ºC
ü
Max. Conductor temp at of Terminator short circuit
for 5 Sec : 250º C
ü
AC Test Voltage : 6.5 kV,50Hz,5min
ü
DC Test Voltage : 15 kV for 5min
ü
Approx Dielectric Strength : 20 kV/ mm
ü
Specification : Generally As per EN 50618
ü
Min. Binding Radius : 5 X Cable OD
ü
Conductor Annealed Tinned Flexible
Copper Conductor
ü
Insulation EBXL - XLPO -Low Smoke
Halogen free\
ü
Core Color Black
ü
Inner sheath Nylon
ü
Outer Sheath EBXL - XLPO -120ºC
ü
Sheath Colour Black With Red Strip
Application
Product Construction
Technical Data
Features
2 X 4
A7891902
0.7
2.5
56/0.31
www.siechem.comConductor
Diameter
(Nom)
No. of Strands /
Strand Dia.
(Max.)
Thickness of
Insulation
Thickness of
Outer Sheath
No. of Cores x
Nominal Cross
Sectional Area
Part number
mm
Nos/mm
mm
Nom
Nom
Min
Min
140
5.09
Overall
Diameter
of Cable
(Nom.)
Approx
Cable
Weight
DC Conductor
Resistance
20°C
(Max)
(6.6 x 13.6) ± 0.6
0.8 0.58
0.53
mm mm
mm
mm
kg/km
Sq.mmSiechem Annealed Tinned Flexible Copper Conductor, EBXL XLPO Insulated, Nylon Inner Sheathed & EBXL XLPO Outer Sheathed
(Twin Parallel) Solar PV Cable.
Ω/km
Catalogue
No.
A789
Siechem Wires & Cables Meet EU RoHS Directive
Lead
Free
Hg
Free
Cd
Free
6+
Cr
Free
PBB
Free
PBDE
Free
:
:
:
:
:
:
ü
Used in Photovoltaic Power Supply systems
Indoor & Out doors
ü
Applicable for Installation in Cable trays,
Conduits, on and in wall as well as for
direct burial
ü
Resistance against UV, Water. Ozone,
Fluids, Oil, Salt & General Weathering
ü
Electron Beam Cross Linked Halogen free,
Flame Retardant, Low Smoke Emission
Fire retardant to meet IEC 607541-1/ EN 50268-2
RoHS Compliant as per EU norms
Resistant to Anti-Rodent and Anti-Termite attacks
ü
Wires & Cables
Siechem 2C X 4 Sqmm Twin Parallel Solar Cable
22
TUV
AS
9100
ISO
45001
ISO
9001
ISO
14001