Catalogue

No

A302

Single Core Aluminium Conductor Electron Beam Cross Linked Solar Cable with Nylon Jacket Constructed

as per EN 50618 & AS/NZS 5000.1 Specification

Construction

Water Resistant & Rodent Resistant

Resistance against UV, Water, Ozone, Fluids, Oil, Salt &

General Weathering.

Electron Beam Cross Linked

Halogen Free, Flame Retardant, Low Smoke Emission

Fire retardant to meet IEC 607541-1/EN 50268-2

RoHS compliant as per EU norms

Max.Temp. at Conductor

Test Voltage

Insulation Resistance Test

Rated Voltage

Max.Short Circuit Temp

Features

: 6500V AC for 5 minutes

:

:

1.0/1.0kV AC,1.5kV DC

+280°C

:

EN 50395

Conductor

Insulation

Sheath

:

:

:

Aluminium Stranded Conductor

according to IEC 60228, Class 2

EBXL - XLPO (Colour Black,Black with Red strip)

EBXL - XLPE 120°C (Colour Red or Black)

Other colours as per customer order

Specification

Siechem Single & Multicore and Screened

Solar Cables Constructed as per

Spec. EN 50618 & AS/NZS 5000.1

120°C (20,000h)

:

Singlecore Solar Cable

Cond. Min.

No. of Wires

Max. DC Conductor

0

Resistance at 20 C

Cable Diameter

(nom.)

Cable Weight

(nom.)

Current Rating

0

In Air at 40 C

Cross Section

Area

Part Number

Sq.mm

Nos.

mm

Kg/Km

Amps

16

25

35

50

70

95

120

150

185

240

300

400

Note : Insulations colour (XX) - Please add two digits in the part number as per the colour code given hereunder replacing XX while ordering Red - 01 & Black - 04

Sheath Colour (YY) please add two digits in the part number as per the colour code given hereunder replacing YY while ordering Black - 04 & Black with Red Stripe - 39

*Nylon jacket & sacrificial PVC are not part of EN specification

6

6

6

6

12

15

15

15

30

30

30

53

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

13.1

15.5

16.5

18.7

20.3

23.4

24.9

27.4

30.0

33.4

36.4

40.6

209

290

338

444

533

703

810

979

1175

1458

1752

2211

09

143

178

217

281

342

399

460

529

627

725

875

Ω/km

A30228XXYY

A30230XXYY

A30232XXYY

A30234XXYY

A30237XXYY

A30238XXYY

A30241XXYY

A30242XXYY

A30244XXYY

A30246XXYY

A30248XXYY

A30249XXYY

*Jacket 1 : Nylon -12 (Black)

*Jacket 2 : Sacrificial PVC (UV Resistant) -Black(Optional)

Used for direct burial

Siechem EBXL XLPO 120°CAluminium Solar Cable

Water, Rodent, Termite & UV Resistant Solar Cables

Wires & Cables

TUV

AS

9100

ISO

45001

ISO

9001

ISO