Wires & Cables
Features
Flame retardant
Self-extinguishing
UV resistant
Outdoor solar applications.
Product Construction
Conductor : Aluminium conductor complying with IEC 60228
Insulation : PVC compound
Bedding : PVC compound
Outer Sheath : PVC compound - Black
Technical Data
Temperature Range:
Flexing : -5°C to + 50°C
Fixed Installation : -40°C to + 70°C
Permissible short circuit : +160°C (Duration 5 secs)
Voltage for Testing : 4 kV
Bending Radius (Min):
Multi Core : 12 x Cable Diameter
Rated Voltage : U /U 600/1000 V
o
13
Volume Resistivity at 27°C(Min) : 1 X 10 Ohm-cm
Application
Power Plants
Industrial and Switching installations
Indoor and outdoor uses
In open air, underground and in water
where mechanical damage is not anticipated.
Secondary distribution networks
Multi Core Stranded Aluminium Conductor PVC Insulated & Sheathed 600/1000V (UA) Power
Cable conforming to IEC 60502 P-1
Part Number
No. of Cores and Cross Section
Area
(sq.mm)Outer Diameter in
(mm) approx.
Weight
(Kg/Km) approx.
26
Catalogue
No
944E
944ES2804
944ES3004
944ES3204
944ES3404
944ES3704
944ES3804
944ES4104
944ES4204
944ES4404
944ES4604
944ES4804
944ES4904
4Cx16
4Cx25
4Cx35
4Cx50
4Cx70
4Cx95
4Cx120
4Cx150
4Cx185
4Cx240
4Cx300
4Cx400
20.8
24.0
26.2
30.5
34.4
39.6
43.2
47.5
53.4
59.5
65.4
75.0
565
760
920
1255
1580
2100
2510
2980
3820
4750
5810
7570
Max. DC Conductor
Resistance at 20°C (Ω/km)
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
Siechem PVC (UA) Aluminium Power Cable
TUV
AS
9100
ISO
45001
ISO
9001
ISO
14001