63

Wires & Cables

Copper conductor

cross section

2

mm

Reduction Factor

Number of

simultaneous

loaded

conductors on

each tray

Installation

Method

1x0

1x0

1

1

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

39

51

68

88

121

161

215

266

336

423

502

589

682

26

34

46

59

81

108

144

178

225

283

336

395

457

23

30

40

52

71

95

127

157

198

250

296

348

402

21

28

37

48

65

87

116

144

181

228

271

318

368

20

26

34

44

61

81

108

133

168

212

251

295

341

18

23

31

40

54

72

97

120

151

190

226

265

307

17

22

29

38

52

69

92

114

144

182

216

253

293

4

0.67

6

0.59

8

0.54

10

0.5

16

0.45

20

0.43

Current capacity in A

Connecting lead in free air or perforated tray

Copper conductor

cross section

2

mm

Reduction Factor

Number of

simultaneous

loaded

conductors on

each tray

Installation

Method

1x0

1x0

Current capacity in A

Connecting lead in free air or perforated tray

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

39

51

68

88

121

161

215

266

336

423

502

589

682

28

36

48

62

86

114

153

189

239

300

356

418

484

23

30

39

51

70

93

125

154

195

245

291

342

396

20

27

35

46

63

84

112

138

175

220

261

306

355

19

24

33

42

58

77

103

128

161

203

241

283

327

16

21

28

36

50

66

88

109

138

173

206

241

280

15

19

26

33

46

61

82

101

128

161

191

224

259

1

1

4

0.71

6

0.58

8

0.52

10

0.48

16

0.41

20

0.38