Table of Contents Table of Contents
Previous Page  62 / 66 Next Page
Information
Show Menu
Previous Page 62 / 66 Next Page
Page Background www.siechem.com

61

Wires & Cables

Construction

Sq.mm

1x0

1.5

2.5

4

6

10

Free Air

On Surfaces without

Opposite Contact

On Surfaces with

Opposite Contact

In Conduict,

Duct

1x0

21

29

39

50

70

21

28

37

48

66

17

23

31

40

56

12

15

20

27

37

Lifetime Expectation

If cross linked wires are used at higher temperatures than indicated by the temperature index of IEC 60216, the lifetime is reduced accordingly, conversely, the

lifetime will increase at lower temperatures. Siechem EBXL Solar cable 125 for example has a life span of 20'000 h at a conductor temperature of +120°C,

which is approx. 2.5 years. If it is used at another temperature, lifetime expectations are as follows:

0

Ambient Temperature 90 C

0

Current Rating 120 C

0

Ambient Temperature 30 C

Construction

Sq.mm

1x0

1.5

2.5

4

6

10

39

51

68

88

121

Free Air

37

48

65

84

115

On Surfaces without

Opposite Contact

26

34

45

59

80

On Surfaces with

Opposite Contact

21

27

36

47

64

In Conduict,

Duct

1x0

Lifetime Expectation

Lifetime in Hours

80

90

100

110

120

130

140

150

160

3

10

4

10

5

10

6

10

Temperature in Degrees

0

Ambient Temperature 60 C

Construction

Sq.mm

1x0

1.5

2.5

4

6

10

Free Air

On Surfaces without

Opposite Contact

On Surfaces with

Opposite Contact

In Conduict,

Duct

1x0

32

42

56

72

99

30

39

53

69

94

21

28

37

48

66

17

22

30

39

52