Single Core Aluminium Conductor EBXL-XLPE 120°C Insulated, HR PVC Sheathed, (UA) UV Resistant

Power Cable

Construction:

Operating Temperature : -15°C to +120°C

High Insulation resistance at elevated temperature

Short Circuit Temperature : 250°C

Bending radius (min) : 12 x Cable dia

Test Voltage : 3 kV for 5 mins.

Technical Data

Conductor

Insulation

Jacket

:

:

:

Aluminium conductor

complying with IS : 8130 - 1984

PVC ST 2 & UV Resistant complying with

IS : 5831 - 1984. (Colour Black)

Optional : 105°C HR PVC (UV)

Electron Beam Cross Linked Polyethylene 120°C

Electron Beam Cross Linked. Does not melt or drip

Enhanced Mechanical, Electrical, Thermal & Weathering

properties.

Flame retardant

Excellent UV and Ozone resistant.

Specially designed for PV Power cable segment.

Features

Applications

PV Power cables

Transmission and distribution of Power

Industrial units

Commercial and residential places

Indoor and outdoor uses

Cable ducts, cable trays and conduits

Direct burial.

Rating factors for variation in ambient air temperature :

0

Temperature - C

Rating

Factors

Conductor

0

Temp. 120

C

20 25 30 35 40 45 50 55 60 65 70 75 80

1.12 1.09 1.06 1.03 1.00 0.97 0.94 0.91 0.88 0.83 0.79 0.75 0.71

Catalogue

No

652S/653S

Wires & Cables

Specification : IS : 7098 (P-1) / 1988 (with enhanced operating temperature)

Siechem

offers 120

°

C

EBXL XLPE as against 90°C

offered by rest of the

competition

Note : Please replace XX in the part number as per the colour code given hereunder.

Red - 01

Yellow - 02

Blue - 03

Black - 04

Green - 05

Yellow-Green - 06

Grey - 07

Siechem EBXLXLPE 120°CAluminium (UA) Power Cable

0

0

Current ratings given in this leaflet are calculated at an ambient air temperature 40 C and ground temperature 30 C

0.38

0.57

0.94

1.5

2.4

3.3

4.7

6.6

9.0

11.3

14.2

17.5

22.6

28.3

37.7

47.2

59.4

Short

Circuit

Rating

for 1 sec

Current Rating

For EBXL - XLPE

Cables (120°C)

Max. D.C

Resistance

at 20 deg.C

Approx.

Capacitance

per phase

Conductor

Area

Cond. Min.

No. of

Wires

Thickness

of EBXL

XLPE

Insulation

(Nom.)

Thickness

of Outer

Sheath

(Nom.)

Approx.

Overall

Diameter

Approx.

Net Wt.

of Cable

Direct in

Ground In Duct

In Air

Sq.mm

Nos

mm

Ohm

/Km

KA

µF/Km

Amps

Amps

Amps

mm

Kg/Km

mm

Part Number

652S19XX04

652S23XX04

652S27XX04

653S28XX04

653S30XX04

653S32XX04

653S34XX04

653S37XX04

653S38XX04

653S41XX04

653S42XX04

653S44XX04

653S46XX04

653S48XX04

653S49XX04

653S50XX04

653S51XX04

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

2.0

2.2

2.4

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.2

2.2

2.2

7.5

8.0

9.0

10.0

11.5

12.5

13.5

15.5

17.0

19.0

21.0

23.0

26.0

28.0

33.0

36.0

40.0

0.29

0.34

0.43

0.51

0.487

0.545

0.586

0.643

0.731

0.755

0.724

0.705

0.764

0.794

0.823

0.835

0.859

7.41

4.61

3.08

1.91

1.20

0.868

0.641

0.443

0.320

0.253

0.206

0.164

0.125

0.100

0.0778

0.0605

0.0469

65

80

90

125

160

190

250

325

415

520

625

750

960

1120

1450

1760

2210

1

1

1

6

6

6

6

12

15

15

15

30

30

30

53

53

53

48

62

74

97

126

152

180

224

267

311

349

398

463

534

611

709

819

57

71

87

112

149

176

212

258

310

351

394

453

522

597

661

754

858

55

68

83

109

143

178

217

281

342

399

460

529

627

725

875

1013

1178