![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0038.jpg)
37
Single Core Aluminium Conductor EBXL-XLPE 120°C Insulated, HR PVC Sheathed (A) UV Resistant
Power Cable
Construction:
Operating Temperature : -15°C to +120°C
High Insulation resistance at elevated temperature
Short Circuit Temperature : 250°C
Bending radius (min) : 12 x Cable dia
Test Voltage : 3 kV for 5 mins.
Technical Data
Conductor
Insulation
Jacket
:
:
:
Aluminium conductor
complying with IS : 8130 - 1984
PVC ST 2 & UV Resistant complying with
IS : 5831 - 1984. (Colour Black)
Optional : 105°C HR PVC (UV)
Electron Beam Cross Linked Polyethylene 120°C
Electron Beam Cross Linked. Does not melt or drip
Enhanced Mechanical, Electrical, Thermal & Weathering
properties.
Flame retardant
Excellent UV and Ozone resistant.
Specially designed for PV Power cable segment.
Features
Applications
PV Power cables
Transmission and distribution of Power
Industrial units
Commercial and residential places
Indoor and outdoor uses
Cable ducts, cable trays and conduits
Direct burial.
Armour
: Non magnetic round wires
Rating factors for variation in ambient air temperature :
0
Temperature - C
Rating
Factors
Conductor
0
Temp. 120
C
20 25 30 35 40 45 50 55 60 65 70 75 80
1.12 1.09 1.06 1.03 1.00 0.97 0.94 0.91 0.88 0.83 0.79 0.75 0.71
Catalogue
No
654SRA/655SRA
Wires & Cables
Specification : IS : 7098 (P-1) / 1988 (with enhanced operating temperature)
Siechem
offers 120
°
C
EBXL XLPE as against 90°C
offered by rest of the
competition
Note : Please replace XX in the part number as per the colour code given hereunder.
Red - 01
Yellow - 02
Blue - 03
Black - 04
Green - 05
Yellow-Green - 06
Grey - 07
0
0
Current ratings given in this leaflet are calculated at an ambient air temperature 40 C and ground temperature 30 C
Short
Circuit
Rating
for 1 sec
Current Rating
For EBXL - XLPE
Cables (120°C)
Max. D.C
Resistance
at 20 deg.C
Approx.
Capacitance
per phase
Conductor
Area
Cond. Min.
No. of
Wires
Thickness
of EBXL
XLPE
Insulation
(Nom.)
Thickness
of Outer
Sheath
(Min.)
Approx.
Overall
Diameter
Approx.
Net Wt.
of Cable
Direct in
Ground In Duct
In Air
Dimension
of
Arm Wire
(Nom.)
Sq.mmNos mm mm
Kg/Km
Ohm
/Km
KA
Amps Amps
Amps
mm
mm
µF/Km
Part Number
654SRA19XX04
654SRA23XX04
654SRA27XX04
655SRA28XX04
655SRA30XX04
655SRA32XX04
655SRA34XX04
655SRA37XX04
655SRA38XX04
655SRA41XX04
655SRA42XX04
655SRA44XX04
655SRA46XX04
655SRA48XX04
655SRA49XX04
655SRA50XX04
655SRA51XX04
0.38
0.57
0.94
1.5
2.4
3.3
4.7
6.6
9.0
11.3
14.2
17.5
22.6
28.3
37.7
47.2
59.4
-
-
0.32
0.38
0.380
0.423
0.464
0.518
0.587
0.616
0.607
0.604
0.657
0.689
0.696
0.716
0.745
7.41
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
10.5
11.0
12.0
12.5
14.5
15.5
17.0
19.5
20.0
22.0
24.0
26.0
29.0
31.0
35.0
38.0
43.0
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.4
1.4
1.4
1.4
1.4
1.56
1.56
1.56
1.72
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.9
2.0
2.1
2.4
2.6
2.8
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
131
152
176
200
287
331
406
523
655
767
907
1067
1322
1522
2015
2465
2969
48
62
74
97
126
152
180
224
267
311
349
398
463
534
611
709
819
57
71
87
112
149
176
212
258
310
351
394
453
522
597
661
754
858
55
68
83
109
143
178
217
281
342
399
460
529
627
725
875
1013
1178
Siechem EBXL XLPE 120°C Aluminium (A) Power Cable
TUV
AS
9100
ISO
45001
ISO
9001
ISO