Menu

Products

More Category
Cables by Segment

TUV 2Pfg1169/08.2007 & EN 50618 Cable

IS : 7098 (Part-1) – Single Core Copper Conductor EBXL XLPE 120°C Insulated, HR PVC Sheathed, (UA) UV Resistant Cable

  • PV Power cables
  • Transmission and distribution of Power Industrial units Commercial and residential places
  • Indoor and outdoor uses
  • Cable ducts, cable trays and conduits
  • Direct burial.

  • Conductor : Annealed Plain Copper conductor complying with IS : 8130 – 1984
  • Insulation : Electron Beam Cross Linked Polyethylene 120°C
  • Jacket : PVC ST 2 & UV Resistant complying with IS : 5831 – 1984. (Colour Black)
    Optional : 105°C HR PVC (UV)
  • Specification : IS : 7098 (P-1) / 1988 (with enhanced operating temperature)

  • Operating Temperature : -15 °C to + 120°C
  • High Insulation resistance at elevated temperature
  • Short Circuit Temperature : 250°C
  • Bending Radius (Min) : 12 x Cable Diameter
  • Voltage for Testing : 3 kV for 5 mins

  • Electron Beam Cross Linked. Does not melt or drip
  • Enhanced Mechanical, Electrical, Thermal & Weathering properties.
  • Flame retardant
  • Excellent UV and Ozone resistant.
  • Specially designed for PV Power cable segment

Part Number Conductor Area Cond. Min.No. of Wires Thickness of EBXL XLPE Insulation (Nom.) Thickness of Outer Sheath (Nom.) Approx.
Overall
Diameter
Approx.
Net Wt.
of Cable
Max. D.C
Resistance
at 20°C
Approx.
Capacitance per phase
Current Rating
For EBXL – XLPE
Cables (120oC)
Short Circuit Rating for 1 sec
Direct in
Ground
In Duct In Air
Sq.mm Nos mm mm mm Kg/Km Ω/Km μF/Km Amps Amps Amps kA
662S13XX04 1.5 1 0.7 1.8 6.8 65 12.1 0.19 39 34 34 0.21
662S16XX04 2.5 1 0.7 1.8 7.2 75 7.41 0.24 53 45 47 0.36
662S19XX04 4 1 0.7 1.8 7.5 95 4.61 0.29 68 60 61 0.57
662S23XX04 6 1 0.7 1.8 8.0 120 3.08 0.34 86 74 78 0.86
663S27XX04 10 6 0.7 1.8 9.0 165 1.83 0.43 112 98 105 1.4
663S28XX04 16 6 0.7 1.8 10.0 225 1.15 0.51 150 126 140 2.3
663S30XX04 25 6 0.9 1.8 11.5 320 0.727 0.487 192 164 191 3.6
663S32XX04 35 6 0.9 1.8 12.5 415 0.524 0.545 229 197 237 5.0
665S34XX04 50 6 1.0 1.8 13.5 545 0.387 0.586 272 234 286 7.1
663S37XX04 70 12 1.1 1.8 15.5 770 0.268 0.643 333 290 367 10.0
663S38XX04 95 15 1.1 1.8 17.0 1000 0.193 0.731 396 344 446 13.6
663S41XX04 120 18 1.2 1.8 19.0 1260 0.153 0.755 449 398 517 17.1
663S42XX04 150 18 1.4 2.0 21.0 1570 0.124 0.724 507 447 597 21.4
663S44XX04 185 30 1.6 2.0 23.0 1910 0.0991 0.705 571 513 680 26.4
663S46XX04 240 34 1.7 2.0 26.0 2410 0.0754 0.764 665 600 803 34.3
663S48XX04 300 34 1.8 2.0 28.0 2980 0.0601 0.794 750 688 927 42.9
663S49XX04 400 53 2.0 2.2 33.0 3970 0.0470 0.823 838 786 1112 57.1
663S50XX04 500 53 2.2 2.2 36.0 4945 0.0366 0.835 941 895 1282 71.4
663S51XX04 630 53 2.4 2.2 40.0 6130 0.0283 0.859 1065 1037 1483 90.0

Current ratings given in this leaflet are calculated at an ambient air temperature 40°C and ground temperature 30°C

Rating factors for variation in ambient air temperature :

Temperature-°C 20 25 30 35 40 45 50 55 60 65 70 75 80
Rating Factors Conductor Temp.120°C 1.12 1.09 1.06 1.03 1.00 0.97 0.94 0.91 0.88 0.83 0.79 0.75 0.71

 

Note : Please replace XX in the part number as per the colour code given hereunder.
Red – 01 Yellow -02 Blue – 03 Black – 04 Green – 05 Yellow-Green – 06 Grey – 07