- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Dimension of Armour Wire |
Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C | Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Ground | In Duct | In Air | In Ground | In Duct | In Air | ||||||||||
Sq.mm | Nos. | mm | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
233ER1304 | 1.5 | 1 | 0.7 | 1.4 | 1.24 | 16.2 | 489 | – | – | – | – | – | – | – | – |
233ER1604 | 2.5 | 1 | 0.7 | 1.4 | 1.24 | 17.7 | 583 | – | – | – | – | – | – | – | – |
233ER1904 | 4 | 1 | 0.7 | 1.4 | 1.24 | 18.6 | 638 | 7.41 | 44 | 37 | 38 | 35 | 29 | 29 | 0.38 |
233ER2304 | 6 | 1 | 0.7 | 1.4 | 1.24 | 20.2 | 777 | 4.61 | 54 | 45 | 49 | 43 | 36 | 38 | 0.57 |
233ER2704 | 10 | 1 | 0.7 | 1.4 | 1.40 | 22.2 | 933 | 3.08 | 71 | 59 | 69 | 56 | 47 | 43 | 0.94 |