Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Ground | In Duct | In Air | In Ground | In Duct | In Air | |||||||||
Sq.mm | Nos. | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
240E2803 | 16 | 6 | 0.7 | 1.8 | 17.7 | 646 | 1.15 | 118 | 97 | 118 | 94 | 77 | 91 | 2.3 |
240E3003 | 25 | 6 | 0.9 | 2.0 | 21.2 | 962 | 0.727 | 151 | 123 | 151 | 120 | 98 | 116 | 3.6 |
240E3203 | 35 | 6 | 0.9 | 2.0 | 23.2 | 1259 | 0.524 | 183 | 149 | 199 | 145 | 118 | 153 | 5.0 |
240E3403 | 50 | 6 | 1.0 | 2.0 | 26.1 | 1711 | 0.387 | 215 | 174 | 228 | 171 | 138 | 175 | 7.1 |
240E3703 | 70 | 12 | 1.1 | 2.2 | 29.1 | 2298 | 0.268 | 267 | 215 | 291 | 212 | 171 | 224 | 10.0 |
240E3803 | 95 | 15 | 1.1 | 2.2 | 32.7 | 3054 | 0.193 | 316 | 255 | 352 | 251 | 202 | 271 | 13.6 |
240E4103 | 120 | 18 | 1.2 | 2.2 | 35.7 | 3781 | 0.153 | 360 | 287 | 410 | 286 | 228 | 315 | 17.1 |
240E4203 | 150 | 18 | 1.4 | 2.4 | 39.4 | 4666 | 0.124 | 407 | 324 | 472 | 323 | 257 | 363 | 21.4 |
240E4403 | 185 | 30 | 1.6 | 2.6 | 43.8 | 5751 | 0.0991 | 456 | 362 | 540 | 362 | 287 | 415 | 26.4 |
240E4603 | 240 | 34 | 1.7 | 2.8 | 48.7 | 7359 | 0.0754 | 527 | 417 | 637 | 418 | 331 | 490 | 34.3 |
240E4803 | 300 | 34 | 1.8 | 3.0 | 53.7 | 9131 | 0.0601 | 593 | 470 | 735 | 471 | 373 | 565 | 42.9 |
240E4903 | 400 | 53 | 2.0 | 3.2 | 60.9 | 12027 | 0.0470 | 660 | 523 | 816 | 524 | 415 | 628 | 57.1 |