- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Dimension of Armour Wire |
Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C | Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Ground | In Duct | In Air | In Ground | In Duct | In Air | ||||||||||
Sq.mm | Nos. | mm | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
243ER1303 | 1.5 | 1 | 0.7 | 1.4 | 1.24 | 15.3 | 470 | 12.1 | 33 | 26 | 27 | 26 | 21 | 21 | 0.21 |
243ER1603 | 2.5 | 1 | 0.7 | 1.4 | 1.24 | 16.2 | 539 | 7.41 | 44 | 37 | 38 | 35 | 29 | 29 | 0.36 |
243ER1903 | 4 | 1 | 0.7 | 1.4 | 1.24 | 17.2 | 626 | 4.61 | 55 | 47 | 49 | 44 | 37 | 38 | 0.57 |
243ER2303 | 6 | 1 | 0.7 | 1.4 | 1.24 | 18.3 | 740 | 3.08 | 69 | 57 | 64 | 55 | 45 | 49 | 0.86 |
244ER2703 | 10 | 6 | 0.7 | 1.4 | 1.24 | 21.8 | 1066 | 1.83 | 92 | 74 | 88 | 73 | 59 | 68 | 1.4 |