- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C | Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Air | In Duct | In Ground | In Air | In Duct | In Ground | |||||||||
Sq.mm | Nos. | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
230E2803 | 16 | 6 | 0.7 | 1.8 | 17.7 | 358 | 1.91 | 91 | 76 | 92 | 70 | 60 | 73 | 1.5 |
230E3003 | 25 | 6 | 0.9 | 2.0 | 21.2 | 512 | 1.20 | 114 | 97 | 117 | 88 | 77 | 93 | 2.4 |
230E3203 | 35 | 6 | 0.9 | 2.0 | 23.2 | 629 | 0.868 | 142 | 116 | 141 | 109 | 92 | 112 | 3.3 |
230E3403 | 50 | 6 | 1.0 | 2.0 | 26.1 | 811 | 0.641 | 173 | 136 | 168 | 133 | 108 | 133 | 4.7 |
230E3703 | 70 | 12 | 1.1 | 2.0 | 29.1 | 1038 | 0.443 | 221 | 168 | 207 | 170 | 133 | 164 | 6.6 |
230E3803 | 95 | 15 | 1.1 | 2.2 | 32.7 | 1343 | 0.320 | 269 | 199 | 246 | 207 | 158 | 195 | 9.0 |
230E4103 | 120 | 15 | 1.2 | 2.2 | 35.7 | 1630 | 0.253 | 311 | 224 | 278 | 239 | 178 | 221 | 11.3 |
230E4203 | 150 | 15 | 1.4 | 2.2 | 39.4 | 1977 | 0.206 | 360 | 255 | 315 | 277 | 202 | 250 | 14.2 |
230E4403 | 185 | 30 | 1.6 | 2.4 | 43.8 | 2435 | 0.164 | 411 | 284 | 354 | 316 | 225 | 281 | 17.5 |
230E4603 | 240 | 30 | 1.7 | 2.6 | 48.7 | 3056 | 0.125 | 484 | 326 | 408 | 372 | 259 | 324 | 22.6 |
230E4803 | 300 | 30 | 1.8 | 2.8 | 53.7 | 3753 | 0.100 | 558 | 369 | 462 | 429 | 293 | 367 | 28.3 |
230E4903 | 400 | 53 | 2.0 | 3.0 | 60.9 | 4856 | 0.0778 | 619 | 410 | 513 | 476 | 325 | 407 | 37.7 |