- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Dimension of Armour Wire |
Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C | Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Ground | In Duct | In Air | In Ground | In Duct | In Air | ||||||||||
Sq.mm | Nos. | mm | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
243ER1302 | 1.5 | 1 | 0.7 | 1.4 | 1.24 | 15.3 | 458 | 12.1 | 39 | 34 | 31 | 31 | 27 | 24 | 0.21 |
243ER1602 | 2.5 | 1 | 0.7 | 1.4 | 1.24 | 16.1 | 520 | 7.41 | 50 | 43 | 43 | 40 | 34 | 33 | 0.36 |
243ER1902 | 4 | 1 | 0.7 | 1.4 | 1.24 | 17.2 | 597 | 4.61 | 66 | 55 | 59 | 52 | 44 | 45 | 0.57 |
243ER2302 | 6 | 1 | 0.7 | 1.4 | 1.24 | 18.6 | 711 | 3.08 | 84 | 68 | 74 | 67 | 54 | 57 | 0.86 |
244ER2702 | 10 | 6 | 0.7 | 1.4 | 1.24 | 20.9 | 936 | 1.83 | 110 | 92 | 101 | 87 | 73 | 78 | 1.4 |
244ER2802 | 16 | 6 | 0.7 | 1.6 | 1.4 | 22.8 | 1161 | 1.15 | 142 | 117 | 137 | 113 | 93 | 105 | 2.3 |