- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Dimension of Armour Strip | Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Ground | In Duct | In Air | In Ground | In Duct | In Air | ||||||||||
Sq.mm | Nos. | mm | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
244WF3003 | 25 | 6 | 0.9 | 4 x 0.8 | 1.4 | 20.0 | 973 | 0.727 | 181 | 150 | 177 | 144 | 119 | 98 | 3.6 |
244WF3203 | 35 | 6 | 0.9 | 4 x 0.8 | 1.4 | 21.6 | 1197 | 0.524 | 219 | 179 | 218 | 174 | 142 | 123 | 5.0 |
244WF3403 | 50 | 6 | 1.0 | 4 x 0.8 | 1.4 | 24.0 | 1551 | 0.387 | 260 | 212 | 267 | 206 | 168 | 149 | 7.1 |
244WF3703 | 70 | 12 | 1.1 | 4 x 0.8 | 1.56 | 26.7 | 1999 | 0.268 | 320 | 262 | 342 | 254 | 208 | 192 | 10.0 |
244WF3803 | 95 | 15 | 1.1 | 4 x 0.8 | 1.56 | 29.8 | 2564 | 0.193 | 378 | 307 | 416 | 300 | 244 | 234 | 13.6 |
244WF4103 | 120 | 18 | 1.2 | 4 x 0.8 | 1.56 | 32.4 | 3103 | 0.153 | 431 | 349 | 485 | 342 | 277 | 273 | 17.1 |
244WF4203 | 150 | 18 | 1.4 | 4 x 0.8 | 1.72 | 35.6 | 3776 | 0.124 | 486 | 394 | 559 | 386 | 313 | 315 | 21.4 |
244WF4403 | 185 | 30 | 1.6 | 4 x 0.8 | 1.88 | 39.4 | 4577 | 0.0991 | 544 | 442 | 641 | 432 | 351 | 361 | 26.4 |
244WF4603 | 240 | 34 | 1.7 | 4 x 0.8 | 2.04 | 43.5 | 5721 | 0.0754 | 629 | 509 | 758 | 499 | 404 | 428 | 34.3 |
244WF4803 | 300 | 34 | 1.8 | 4 x 0.8 | 2.20 | 47.8 | 6977 | 0.0601 | 711 | 575 | 876 | 564 | 456 | 494 | 42.9 |
244WF4903 | 400 | 53 | 2.0 | 4 x 0.8 | 2.36 | 53.8 | 9038 | 0.0470 | 834 | 668 | 974 | 622 | 530 | 549 | 57.1 |