- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Air | In Duct | In Ground | In Air | In Duct | In Ground | |||||||||
Sq.mm | Nos. | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
230E2802 | 16 | 6 | 0.7 | 2.0 | 20.8 | 499 | 1.91 | 108 | 92 | 110 | 83 | 73 | 87 | 1.5 |
230E3002 | 25 | 6 | 0.9 | 2.0 | 19.6 | 405 | 1.20 | 127 | 116 | 140 | 98 | 92 | 111 | 2.4 |
230E3202 | 35 | 6 | 0.9 | 2.0 | 21.2 | 488 | 0.868 | 160 | 139 | 168 | 123 | 110 | 133 | 3.3 |
230E3402 | 50 | 6 | 1.0 | 2.0 | 23.6 | 617 | 0.641 | 194 | 165 | 198 | 149 | 131 | 157 | 4.7 |
230E3702 | 70 | 12 | 1.1 | 2.0 | 26.3 | 782 | 0.443 | 250 | 204 | 244 | 192 | 162 | 194 | 6.6 |
230E3802 | 95 | 15 | 1.1 | 2.0 | 29.1 | 980 | 0.320 | 304 | 239 | 290 | 234 | 190 | 230 | 9.0 |
230E4102 | 120 | 15 | 1.2 | 2.2 | 32.1 | 1210 | 0.253 | 355 | 272 | 330 | 273 | 216 | 262 | 11.3 |
230E4202 | 150 | 15 | 1.4 | 2.2 | 35.3 | 1457 | 0.206 | 410 | 306 | 373 | 315 | 243 | 292 | 14.2 |
230E4402 | 185 | 30 | 1.6 | 2.2 | 38.8 | 1743 | 0.164 | 469 | 344 | 418 | 361 | 273 | 332 | 17.5 |
230E4602 | 240 | 30 | 1.7 | 2.4 | 43.2 | 2202 | 0.125 | 556 | 396 | 483 | 428 | 314 | 383 | 22.6 |
230E4802 | 300 | 30 | 1.8 | 2.6 | 47.6 | 2686 | 0.100 | 642 | 446 | 546 | 494 | 354 | 433 | 28.3 |
230E4902 | 400 | 53 | 2.0 | 2.8 | 53.7 | 3478 | 0.0778 | 714 | 495 | 606 | 549 | 393 | 481 | 37.7 |