- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Sheath Thickness (Nom.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Air | In Duct | In Ground | In Air | In Duct | In Ground | |||||||||
Sq.mm | Nos. | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
229E1302 | 1.5 | 1 | 0.7 | 1.8 | 13.2 | 197 | – | – | – | – | – | – | – | – |
229E1602 | 2.5 | 1 | 0.7 | 1.8 | 13.9 | 222 | – | – | – | – | – | – | – | – |
229E1902 | 4 | 1 | 0.7 | 1.8 | 14.9 | 254 | 7.41 | 38 | 37 | 44 | 29 | 29 | 35 | 0.38 |
229E2302 | 6 | 1 | 0.7 | 1.8 | 15.9 | 292 | 4.61 | 49 | 45 | 54 | 38 | 36 | 43 | 0.57 |
229E2702 | 10 | 1 | 0.7 | 1.8 | 17.5 | 360 | 3.08 | 69 | 59 | 71 | 53 | 47 | 56 | 0.94 |