- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
Part Number | Area (Nom.) | Min. No.of Wires | Insulation Thickness (Nom.) | Dimension of Armour Wire | Sheath Thickness (Min.) | Approx.Overall Diameter | Approx.Weight of Cable | Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) | Current Rating for Chemically Cured XLPE Cables(90°C) | Short Circuit Rating for 1sec | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
In Air | In Duct | In Ground | In Air | In Duct | In Ground | ||||||||||
Sq.mm | Nos. | mm | mm | mm | mm | Kg/Km | Ω/km | Amps | Amps | KA | |||||
233ER1302 | 1.5 | 1 | 0.7 | 1.4 | 1.24 | 14.8 | 431 | – | – | – | – | – | – | – | – |
233ER1602 | 2.5 | 1 | 0.7 | 1.4 | 1.24 | 16.1 | 502 | – | – | – | – | – | – | – | – |
233ER1902 | 4 | 1 | 0.7 | 1.4 | 1.24 | 16.6 | 534 | 7.41 | 38 | 37 | 44 | 29 | 29 | 35 | 0.38 |
233ER2302 | 6 | 1 | 0.7 | 1.4 | 1.24 | 17.6 | 593 | 4.61 | 49 | 45 | 54 | 38 | 36 | 43 | 0.57 |
233ER2702 | 10 | 1 | 0.7 | 1.6 | 1.4 | 19.6 | 773 | 3.08 | 69 | 59 | 71 | 53 | 47 | 56 | 0.94 |