Menu

Products

More Category
Cables by Segment

IS 1554-1

PW 125 EBXL ZHLS+FR+HR+125°C 1100 V Single and Multicore Flexible Cables

  • PW 125 Flexible Single and Multicore Electron Beam Cross Linked, Halogen-free very high and low temperature resistant cables are used for
    internal wiring for high rise Buildings, Shopping Malls, Public Buildings, Petro Chemical Plants, Fire prone areas, Fuel Dispencing Bunks, Airports, Crowded
    Public places, Schools, Power Stations, Sensor leads, Solenoid valves, Hospitals, Signal Systems, heaters, Lighting fixtures, Plant and Machinery, Outdoor
    Traffic systems, Motor Winding, White goods, Control panels, Switchboards & Industrial applications etc.

  • Conductor: Flexible Bare Copper Conductor as per IS 8130, BS 6360, IEC 60228 & BS EN 60228 bare conductor construction according to SAE J1128
  • Insulation: EBXL – ZHLS + FR+HR + 125°C
  • Separator: Polyester Tape (for multicore cable)
  • Sheath: EBXL – ZHLS + FR+HR + 125°C (for multicore cable)
  • Colour : As per customer order

  • Temperature Range : – 40°C to +125°C
  • Voltage Rating: 1100V
  • Test Voltage: 3.5kV for 5 minutes
  • Standard: Generally as per IS 694, FRLS

  • Operating temperature – 40°C to +125°C (20,000 hours)
  • Flame retardant and Halogen free, Very low smoke
  • Non Toxic
  • Weather resistant
  • High abrasion resistance
  • Ozone & UV resistant
  • Oil & grease resistant
  • High tracking resistance
  • Easily strippable & very flexible
  • Hot pressure resistant
  • Soldering iron resistant
  • High current carrying capacity
  • Short Circuit resistance upto +280°C for 60 sec.

PW125 SINGLE CORE FLEXIBLE CABLES

Part No. Size No. of Strands/Nom. strand dia. Nominal Insulation thickness Maximum Overall Cable Diameter Max. DC resistance at 20°C  Current Rating     Other Brands PVC/FR/FRLS Current Rating
Sq.mm  Nos/mm  mm  mm  Ω/km  Amps  Amps 
11208XX* 0.75 24/0.20 0.6 2.8 26.0 24 7
11210XX 1 32/0.20 0.6 3.0 19.5 29 12
11213XX 1.5 30/0.25 0.6 3.4 13.3 36 16
11216XX 2.5 50/0.25 0.7 4.1 7.98 49 22
11219XX 4 56/0.30 0.8 4.8 4.95 66 29
11223XX 6 84/0.30 0.8 5.3 3.30 85 37
11227XX 10 80/0.40 1.0 7.0 1.91 121 51
11228XX 16 126/0.40 1.0 8.1 1.21 163 65
11230XX 25 196/0.40 1.2 10.2 0.780 219 90
11232XX 35 276/0.40 1.2 11.7 0.554 272 110
11234XX 50 396/0.40 1.4 13.9 0.386 344 137
11237XX 70 360/0.50 1.4 16.0 0.272 439 215
11238XX 95 475/0.50 1.6 18.2 0.206 523 260
11241XX 120 608/0.50 1.6 20.2 0.161 621 305
11242XX 150 756/0.50 1.8 22.5 0.129 723 355
11244XX 185 925/0.50 2.0 24.9 0.106 825 415
11246XX 240 1221/0.50 2.2 28.4 0.0801 996 500
11248XX 300 1525/0.50 2.4 31.0 0.0641 1150 585

PW125 MULTICORE FLEXIBLE CABLES

Part No. Size No. of strands/Nom. strand dia. Nom. Insulation thickness Nominal Sheath thickness Maximum overall diameter Max. DC conductor resistance at 20°C Current rating
Sq.mm Nos/mm mm 2 Core 3 Core 4 Core 2 Core 3 Core 4 Core Ω/km 2 Core 3 & 4 Core
mm mm mm mm mm mm Amp Amp
13508XX* 0.75 24/0.20 0.6 0.9 0.9 0.9 7.3 7.7 8.4 26.0 19 17
13510XX 1 32/0.20 0.6 0.9 0.9 0.9 7.6 8.1 8.8 19.5 23 20
13513XX 1.5 30/0.25 0.6 0.9 0.9 1.0 8.9 9.4 10.4 13.3 29 25
13516XX 2.5 50/0.25 0.7 1.0 1.0 1.0 10.3 10.9 12.0 7.98 39 34
13519XX 4 56/0.30 0.8 1.0 1.0 1.0 11.6 12.4 13.6 4.95 53 46
13523XX 6 84/0.30 0.8 1.1 1.2 1.2 13.0 13.8 15.5 3.30 68 60
13527XX 10 80/0.40 1.0 1.3 1.4 1.4 16.5 17.7 19.5 1.91 97 85
13528XX 16 126/0.40 1.0 1.4 1.4 1.4 19.4 20.6 23.0 1.21 130 114
13530XX 25 196/0.40 1.2 1.4 1.5 1.6 23.8 25.6 28.5 0.780 175 153
13532XX 35 276/0.40 1.2 1.6 1.6 1.7 27.2 29.3 32.7 0.554 218 190
13534XX 50 396/0.40 1.4 2.0 2.0 2.0 32.0 34.6 38.6 0.386 275 241
Note : XX* : Please add last two digits in the part number as per the colour code given hereunder replacing XX while ordering.
Red – 01 Yellow – 02 Blue – 03 Black – 04 Green – 05 Yellow-Green – 06 Grey – 07 Brown – 08 White – 09 Orange – 10 Violet – 11
Chocolate – 12 Tan – 13 Charcoal – 14 LT Blue – 15 DK Grey – 16 LT Green – 17 DK Green – 18 DK Blue – 19 Purple – 20 Pink – 21
Note : XX* : For Multicore, please add last two digits in the part number as per the number of cores given hereunder replacing XX while ordering.
Two core – 02 Three core – 03 Four core – 04

Other length as per Customer order.

Current Carrying capacity given is for the maximum conductor operating temperature of 80°C and ambient air temperature of 30°C.


Enquiry

  • flipbook

Call us now Email us now

Enquiry

Enquiry about this Product

CAPTCHA Image