- Intended for use as battery cable. PPL.
Part Number |
Conductor Construction | Insulation Wall Thickness Nom. |
Nominal Thickness of sheath |
Cable | Max. Conductor Resistance at 200C |
Current Carrying Capacity |
Standard Length* |
|||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Cross- Section |
No. of Strands |
Diameter of Single wire max. |
Overall Diameter Nom |
Weight Approx. |
||||||
mm2 | nos. | mm | mm | mm | mm | kg/km | Ω/km | Amps | mtrs | |
86427XXYY* | 10 | 74 | 0.41 | 0.7 | 0.8 | 7.3 | 121 | 1.78 | 60 | 500 |
86428XXYY* | 16 | 118 | 0.41 | 0.7 | 0.8 | 8.3 | 180 | 1.21 | 76 | 500 |
86430XXYY* | 25 | 183 | 0.41 | 0.7 | 0.8 | 9.7 | 280 | 0.78 | 96 | 500 |
86432XXYY* | 35 | 259 | 0.41 | 0.7 | 0.8 | 10.9 | 360 | 0.554 | 120 | 500 |
86434XXYY* | 50 | 382 | 0.41 | 0.8 | 1.0 | 13.0 | 510 | 0.386 | 155 | 500 |
86437XXYY* | 70 | 323 | 0.51 | 0.8 | 1.6 | 16.2 | 750 | 0.272 | 195 | 500 |
86438XXYY* | 95 | 421 | 0.51 | 0.9 | 1.6 | 18.7 | 950 | 0.206 | 240 | 500 |
Note : XX*YY* : Please add last two digits in the part number as per the colour code given hereunder replacing XX while ordering. | |||
Red – 01 | Yellow – 02 | Blue – 03 | Black – 04 |
Green – 05 | Yellow-Green – 06 | Grey – 07 | Brown – 08 |
White – 09 | Orange – 10 | Violet – 11 | Chocolate – 12 |
Tan – 13 | Charcoal – 14 | LT Blue – 15 | DK Grey – 16 |
LT Green – 17 | DK Green – 18 | DK Blue – 19 | Purple – 20 |
Pink – 21 |
Other length as per Customer order.
Current Carrying capacity given is for the maximum conductor operating temperature of 80°C and ambient air temperature of 40°C.