- Used for the internal wiring of electric motors and transformers as well as electrical appliances.
- Used for panels cabinets stranding.
Part Number |
Size | Max. Conductor Diameter | Thickness of Insulation (Nom) | Overall Diameter | Max. Conductor Resistance at 20°C |
Weight Approx |
|
---|---|---|---|---|---|---|---|
Min. | Max. | ||||||
mm2 | mm | mm | mm | mm | Ω/km | kg/km | |
A03913XX | 1.5 | 1.5 | 0.7 | 2.6 | 3.2 | 12.1 | 22 |
A03916XX | 2.5 | 1.9 | 0.8 | 3.2 | 3.9 | 7.41 | 34 |
A03919XX | 4 | 2.4 | 0.8 | 3.6 | 4.4 | 4.61 | 48 |
A03923XX | 6 | 2.9 | 0.8 | 4.1 | 5.0 | 3.08 | 68 |
A03927XX | 10 | 3.7 | 1.0 | 5.3 | 6.4 | 1.83 | 110 |