Cables by Segment Cables by Standard

BS 5467

BS 5467 – 3 Core Round Aluminium Conductor Unarmoured Cable

  • Transmission and distribution of Power Industrial units
  • Commercial and residential places
  • Indoor and outdoor uses
  • Cable ducts, cable trays conduits
  • Direct burial and underground burial where mechanical damage risk for cables.

  • Conductor : Aluminium conductor complying with BS 6360
  • Insulation : Electron Beam Cross Linked Polyethylene 120°C
  • Inner sheath : PVC
  • Outer sheath : PVC Type 9 complying with BS 7655-4.2 (Colour-Black)

  • Operating Temperature : -15°C to +120° C
  • High Insulation resistance at elevated temperature
  • Short Circuit Temperature : 250°C
  • Bending radius (min) : 12 x Cable dia
  • Rated Voltage :600/1000 V
  • Test Voltage : 3.5 kV for 5 mins.
  • Specification : BS 5467

  • Electron Beam Cross Linked
  • Enhanced Mechanical, Electrical, Thermal & Weathering properties.
  • Soldering iron resistant
  • Resistance to corona effect.
  • Easy jointing & termination
  • Better resistance to most chemicals & acids
  • Low direct electric losses.
  •  High current carrying capacity.

Part
Number
Area
Cond.Min.
No.of
Wires
Thickness
of EBXL-
XLPE
Insulation
(Nom.)
Thickness
of Outer
Sheath (Nom.)
Approx
Overall
diameter
Approx.Net
Wt.of
Cable
Max.D.C
Resistance
at 20°C
Current Rating For EBXL-XLPE
Cables (120°C)
Current Rating For Chemically Cured XLPE Cables (90°C)
Short Circuit
Rating for 1 sec
Direct in
Ground
In
Duct
In
Air
Direct in
Ground
In
Duct
In
Air
Sq.mm Nos mm mm mm Kg/Km Ω/Km A A A A A A kA
758E1903 4 1 0.7 1.8 14.0 217 7.41 44 37 38 35 29 29 0.38
758E2303 6 1 0.7 1.8 15.2 259 4.61 54 45 49 45 36 38 0.57
758E2703 10 1 0.7 1.8 17.2 335 3.08 71 59 69 56 47 53 0.94
759E2803 16 7 0.7 1.8 19.7 446 1.91 92 76 91 73 60 70 1.5
759E3003 25 7 0.9 1.8 23.4 626 1.20 117 97 114 93 77 88 2.4